Made in EgyptIEC 60947-1 / -3
Fuse switch disconnectors
EFS-V3/400
Fuse switch disconnector
EFS-V3/400 fuse switch disconnector for size NT2 fuse links: 400 A rated operation current at 400 V AC (AC-23B), 3 poles, 28 W power loss, to IEC 60947-1 / -3.
- Rated current
- 400A
- Fuse size
- NT2
- Power loss
- 28W
- Poles
- 3
Technical data
Technical specifications.
Ratings
- Rated operation current
- 400A
- Fuse size
- NT2
- Power loss
- 28W
- Short-circuit capacity @ 400 V
- ≥ 50kA
- Protected short-circuit making · Icw
- 120kA
- Rated isolation voltage · Ui
- 1000V
- Rated impulse withstand · Uimp
- 12kV
- Fuse-link rated voltage · Ue
- 400V
- Frequency
- 50/60Hz
- Poles
- 3
- Protection ON / OFF
- IP20 / IP30
- Standard
- IEC 60947-1 / -3
Working conditions
- Ambient temperature
- −5 ~ +55 °C
- Working mode
- Continuous
- Operation
- Handle
- Installation
- Vertical
- Altitude
- ≤ 2000 m
- Pollution degree
- 3
- Overvoltage level
- IV
Selection table
Rated operation current.
By rated operational voltage (Ue) and utilization category.
| Ue | Utilization | EFS-V3/250 | EFS-V3/400 | EFS-V3/630 |
|---|---|---|---|---|
| 400 V AC | AC-23B | 250 A | 400 A | 630 A |
| 500 V AC | AC-22B | 250 A | 400 A | 630 A |
| 690 V AC | AC-21B | 200 A | 315 A | 500 A |
- Thermal current with fuse link (Ith) equals rated operation current (Ie).
Dimensions
Dimensional drawing
- Width
- 100 mm
- Depth
- 200 mm
- Overall height
- 700 mm
- Phase pitch
- 210 mm
- Top to first terminal
- 70 mm
- Bottom terminal offset
- 57 mm
- Depth when open
- 340 mm
- Opening angle
- 60°
Where it's used
Applications & sectors
- Industrial
- Oil & gas
- Power distribution
- Data centres
- Rail & transport
- Renewable energy
Supporting documents
Technical documents.
Download the datasheet, drawing and certificates for this product.
Browse full technical libraryNext step
Proceed with documents or enquiry.
Share the required standard, quantity, or project deadline and ETAL will route your request to the right sales or engineering contact.